System Concept for HIQuad X
HI 803 211 E Rev. 1.01.00 Page 27 of 110
Air intake filter mounted in the control cabinet door
Air flow
Fuse and power distribution modules K 7205, K 7206, K 7212, K 7213 or K 7214
Air exhaust through the HIMA K 9202B cabinet fan for mounting on the top internal section
of the control cabinet
Required clearance for air intake and air exhaust
Figure 12: Fan Concept within the Control Cabinet
Total power dissipation
Maximum power dissipation per
extension rack
Fan components
< 300 W
< 50 W
3 x K 9203A
300…500 W
< 50 W
3 x K 9203A + K 9202B
500…1000 W
< 100 W
3 x K 9203A + K 9202B
Table 3: Fan Components as a Function of Power Loss
When installing I/O modules, always observe the special instructions specified in the
corresponding data sheets, e.g., additional fans may be required depending on the module
type.
If processor modules, I/O processing modules or communication modules report that the
temperature limits have been exceeded for a longer period of time, the existing ventilation
concept must be reviewed.