System  Product Description 
HI 803 211 E Rev. 1.01.00  Page 31 of 110 
4.2.1  H51X Backplane 
The following figure shows the rear side of the H51X backplane: 
  System bus connections 
Sys. A DOWN (XD1) 
Sys. B DOWN (XD2) 
Sys. A UP (XD3) 
Sys. B UP (XD4) 
  XG1 (DATA) Not applicable (for future use)! 
  5 V power supplies for extension racks, XG2 
and XG3 
  Reference potential (GND) for extension racks, 
XG4 and XG5 
  Connection to L- reference potential (24 V 
supply), XG9 
  Clamp terminal block for redundant 24 V power 
supply, XG10 
  Control cabinet diagnostics for future 
applications, XG8 (loop) Not applicable (for 
future use) 
  24 V power supply (LS1, LS2) for the F-IOP 01 
modules in the extension racks, XG7 (buffer 
module in slot 6 supplies LS1 and buffer module 
in slot 7 supplies LS2) 
  Signaling relay contacts for F-PWR 02, XG6 
Figure 15:  Rear View of H51X Backplane 
4.2.1.1  Supply of the H51X Base Rack 
For supply and power distribution, HIMA recommends using the following components: 
  K 7205: Redundant supply up to a maximum of 63 A total current with fuse protection of up 
to 18 individual circuits with circuit breakers. 
  K 7212: Redundant supply up to a maximum of 35 A total current with 2 decoupling diodes 
and 2 mains filters, with fuse protection of up to 12 individual circuits with circuit breakers. 
  K 7213: Redundant supply up to a maximum of 35 A total current with fuse protection of up 
to 12 individual circuits with circuit breakers. 
  K 7214: Redundant supply up to a maximum of 150 A total current with fuse protection of up 
to 18 individual circuits with circuit breakers. 
The 24 V power supply is connected to the following terminals: 
Table 7:  Connection to the 24 V Power Supply