Page 72 of 110 HI 803 211 E Rev. 1.01.00
System parameters
S
1)
Description
Setting for safe
operation
Start Allowed
Y
TRUE:
Cold start or warm start permitted with the PADT
in RUN or STOP.
The default setting is TRUE.
Application-
specific
FALSE:
Start not allowed.
Load Allowed
Y
TRUE:
Configuration download is allowed.
The default setting is TRUE.
Application-
specific
FALSE:
Configuration download is not allowed.
Reload Allowed
Y
TRUE:
Configuration reload is allowed.
The default setting is TRUE.
Application-
specific
FALSE.
Configuration reload is not allowed.
A running reload process is not aborted when
switching to FALSE.
Global Forcing
Allowed
Y
TRUE:
Global forcing is permitted for this resource.
The default setting is TRUE.
Application-
specific
FALSE:
Global forcing is not permitted for this resource.
Global Force
Timeout Reaction
N
Specifies how the resource should behave when the global
force timeout has expired:
Stop Forcing Only.
Stop Forcing and Stop Resource.
Default value: Stop Forcing Only.
Application-
specific
Minimum
Configuration
Version
N
The default setting is based on the current SILworX version.
It ensures compatibility with future SILworX versions.
Code is generated in accordance with SILworX V10
conventions, since HIQuad X is supported as of SILworX
V10.
Any setting to a SILworX version prior to V10 is rejected for
HIQuad X. An error message is displayed in the logbook!
For more details, refer to Chapter 6.1.3.5.
Application-
specific
Fast Start-Up
N
Not applicable to HIQuad X.
-
1)
The operating system handles the system parameter in a safety-related manner, yes (Y) or no (N)
Table 24: Resource System Parameters