Product Description  System 
Page 46 of 110  HI 803 211 E Rev. 1.01.00 
4.3.6  Redundant H41X Base Rack (24 VDC) 
The I/O processing module in the H41X base rack and that in the extension rack must be 
powered from different power supply units to implement redundant I/O levels in the 
HIQuad H41X system. To this end, e.g., the I/O processing module in the H41X base rack can 
be connected to L1+ (terminal XG5.13) and the I/O processing module in the extension rack 
(terminals XG.3, L+), see Figure 20. The power supply units must be able to bridge voltage 
dropouts of up to 20 ms. 
 
  Inline terminals XG5.1…XG5.13 to 24 V power supply, XG5.13 for connecting to the I/O processing 
module in the H41X base rack 
  Connection to redundant power supply units, see Figure 20 
  Terminal XG.3 (L+) for connecting to 24 VDC for the I/O processing module in extension rack 1 
  Redundant power supply of the F 7133 power distribution modules, insert jumpers in accordance with 
the application 
  Reference potential L- 
Figure 26:  Redundant Connection to H41X Base Rack and Extension Rack 1