System Programming
HI 803 211 E Rev. 1.01.00 Page 79 of 110
Power Supply Input
Voltage 1…5[D20_0004,
#580]
Value of the input voltage in the respective F-PWR 01
power supply unit expressed in mV.
Power Supply
Status[D20_0004, #579]
Status of the F-PWR 01 power supply units. 3 adjacent
bits are coded for each power supply unit.
Status of power supply unit 1
Status of power supply unit 2
Status of power supply unit 3
Status of power supply unit 4
Status of power supply unit 5
The following applies to each power supply unit:
Once the power supply unit has been detected, the
least significant bit is 1. Otherwise, it is bit 0.
If at least one warning was issued for the power
supply unit, the middle bit is 1. Otherwise, it is bit 0.
If at least on fault occurred in the power supply unit,
the most significant bit is 1. Otherwise, it is bit 0.
Main enable switch of the processor module
The subordinate enable switches may be
changed.
The subordinate enable switches may not
be changed.
The following operator functions are locked:
Stop, Start, Download.
The following operator functions are
unlocked: Stop, Start, Download.
Bit-coded redundancy state of the processor modules.
The variable exists depending on the controller family.
Reload is allowed to load a controller.
Reload is not allowed to load a controller.
The current cycle is the first cycle after a
reload.
Responsible Module
Essential
Essential state of redundant processor modules. The
variable exists depending on the controller family.
Safety time set for the resource in ms.
The processor module may be started
through the PADT.
The processor module may not be started
through the PADT.
The current cycle is the first cycle after the
start.
Power Supply State [1]…[2]
Bit-coded state of the power supply of processor
modules 1…2.
The following properties differ depending on the
controller family:
- Possible number of processor modules.
- State bits suitable for safety functions!
System ID of the controller, 1…65 535.