Chapter 6 Communication Mode
6 - 73
While modbus slave operation
Error code is indicated in high byte of status area WXus2, 3. (If error level is warning, EH-SIO keeps working.) If
the next query is processed properly, error code in WXus2, 3 is cleared. If TRNS 9 command is issued while
modbus slave mode, “Invalid command error (H50)” is given in the return code area of TRNS 9 command.
Table 6.18 Abnormalities during modbus slave mode operation
Operation of EH-SIO stops due to serious error of CPU module.
MPU in EH-SIO does not work due to watchdog timer error.
Error is detected in system OS of EH-SIO.
EH-SIO detected a parity error in query (
received message
).
EH-SIO detected a framing error in query (
received message
).
EH-SIO detected an overrun error in query (
received message
).
EH-SIO detected a validity abnormality in the check code of query
(
received message
).
Data receiving was not completed with in specified time.
Transmitting
timeout error
Response sending was not completed with in specified time.
Query (received message) has wrong data
« Note »
Error is checked in every byte. Different from modbus master mode or free protocol mode, only the latest error is
indicated in modbus slave mode. So if parity error or framing error is detected, it can be cleared check code error.
Please check the transmission format configuration and the transmission speed also in case of check code error.