EasyManua.ls Logo

Hitachi EH-150 Series - Error Detection in Simple Data Link Mode

Hitachi EH-150 Series
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6 Communication mode
6 - 101
Simple data link
6.6.6 Error detection in simple data link mode
As described before, data link is operated by using Hi-Protocol communication. EH-SIO detects errors from salve
stations. In case sending request has an error, error code will be stored in WRF000 in each slave station (self-
diagnostic error code). Refer to the instruction manual for detailed information of the error code.
In this section, error information detected by EH-SIO is described.
Error in initial setting
Detail error information can be confirmed by referring the execution result of TRNS 9 command of t parameter,
return code of s parameter and receiving data area. In case of error bit (t+2) is turned ON after execution of TRNS 9
command, there is some detected error.
Table 6.29 Simple data link mode initial setting error table
No.
Error
Code
Name
Error
level
Detail contents
1
HFF
CPU error
---
EH-SIO operation has been stopped due to the error detection of
CPU module (L.RES ON) was done.
2
---
Watch dog timer error
Fatal
Failure
MPU of EH-SIO cant operate according the system program
anymore, EH-SIO has detected watch dog timer error of MPU.
3
H03
OS system error
Fatal
Failure
EH-SIO has detected an error of system OS.
4
H50
Invalid command
specifying error
Warning
TRNS 9 command has been executed at the port specified as
slave function or simple data link function.
5
H51
Over flow error of
number of specified
functions
Warning
There is no EH-SIO mounting, over flow of number of specified
functions such as slave function or simple data link function.
6
H81
Non-supported
command error
Warning
-Non-supported command by EH-SIO has been specified.
-Multiple initial settings have been done wit same port even if the
first initial setting has been done. (more than twice execution of
initial setting)
7
H82
Initial setting error
Warning
-The parameter of initial setting of EH-SIO was illegal.
-The other command has been executed for a port except initial
command before the completion of initial setting.

Table of Contents