Chapter 6 Communication Mode
6 - 54
6.4.3 Initial setting
EH-SIO becomes idle status (waiting to be initial setting by CPU module) after power ON.
In modbus slave mode, EH-SIO works while CPU module in stop mode. Communication mode is cleared by reset
button or rebooting the power.
« Note »
EH-SIO will not receive any operation command from CPU module or external device before initial setting.
Parameters for initial setting
Table 6.15 Parameter table for initial setting
Set Modbus slave mode (H0011)
Select ASCII mode or RTU mode
Note : Only RTU mode is available in software ver. 1.0
Set node number (station number)
Waiting time from receiving a query to sending response.
I/O mapping information
(Bit)
Please specify, when you assign a coil (bit data) to I/O other than a default.
* The I/O mapping function has not been supported in software ver. 1.0.
Set H0000 in software ver. 1.0
I/O mapping information
(Word)
Please specify, when you assign a register (word data) to I/O other than a default.
* The I/O mapping function has not been supported in software ver. 1.0.
Set H0000 in software ver. 1.0
Parameter of TRNS 9 command for initial setting
Command number of initial setting in s+7 is H0000
Be sure to set parameters in the sending data area (s+9 to s+A) according to the next page, and be sure to set
dummy parameter in the receiving data area (s+B to s+D) although nothing is stored in the configured address area.
Figure 6.52 s parameter format (Modbus slave / Initial setting)
« Note »
Although "receiving data area" is not used in Modbus slave mode, configure a dummy address in it.
(data in this address has nothing to do with TRNS 9 command.)
Size of receiving data area
Top I/O address of
receiving data area
Top I/O address of
sending data area