Chapter 6 Communication mode
6 - 78
6.5.4 Initial setting
After power activated, EH-SIO enters idle status (waiting initial setting by CPU module). EH-SIO starts
Hi-Protocol mode operation by initial setting from CPU module.
During Hi-Protocol mode, EH-SIO continues this mode even if CPU module is in stop mode. To change the
communication mode of EH-SIO, power rebooting or reset operation of EH-SIO is requested.
« Note »
EH-SIO will not receive any command from CPU module except initial setting command before initial setting is
completed. At that time, EH-SIO will not receive any command from connected external device.
Parameters for initial setting
Table 6.20 The table of parameter for initial setting
EH-SIO works according to this communication mode.
Specify Hi-Protocol Mode
Select usage of task code with station number or without station number.
In case of task code communication with station number, specify station number.
Parameters of TRNS9 command for initial setting
Initializing command (specified as s+7) is H0000.
Be sure to set parameters in the sending data area (s+9 to s+A) according to the next page, and be sure to set
dummy parameter in the receiving data area (s+B to s+D) although nothing is stored in the configured address area.
Figure 6.59 Parameters of Hi-Protocol mode initial setting
« Note »
Although "receiving data area" is not used in Hi-Protocol mode, configure a dummy address in it.
(Data in this address has nothing to do with TRNS 9 command.)
Size of receiving data area
Top I/O address of
receiving data area
Top I/O address of
sending data area