Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 163
May 2019
If the RS-485 network to slave devices is intermittent or fails completely over short durations and
recovers after the controller is power cycled, use an external isolator with additional port biasing.
See Figure 93.
Note: Legacy Controllers do not provide biasing.
.
Figure 93 - RS-485 Modbus slave wiring with isolation