1. Associated AI blocks that are
configured as T/Cs set their fail
pin on, their warn pin off, and
their output pin to the failsafe
value.
2. Associated AI blocks that are
configured as T/Cs set their IO
status to either:
“CJ High Temperature” if one
of the two CJs on an AI card is
indicating a temperature
greater than 70 degrees C
“CJ Failure” if both CJ
sensors are failing to convert.
3. Associated rack monitor
block’s module fail pin is
turned on.
4. Associated rack monitor
block’s RACK OK pin is turned
off.
5. Associated rack monitor
block’s HITEMP pin is turned
on.
6. ASYS and FSYS blocks’
HITEMP pins are turned on.
7. ASYS and FSYS blocks’ HW
OK pins are turned off.
1. Associated rack monitor
block’s RACK OK pin is turned
off.
2. ASYS and FSYS blocks’ HW
OK pins are turned off.
1. Associated rack monitor
block’s RACK OK pin is turned
off.
2. ASYS and FSYS blocks’ HW
OK pins are turned off.
Locate the Scanner 2 that
indicates a bad power-supply
diagnostic, and replace the
defective supply.