EasyManua.ls Logo

Honeywell 900U02-0100 - Page 209

Honeywell 900U02-0100
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 195
May 2019
Number
of Red
Strobes
Possible Causes
Lead and/or Reserve
Controller Action(s)
User Action
Honeywell OI
Indication
HCDesigner/HC
Utilities
Indication
8 or 9
If 8 flashes, the S1
serial port is
reporting a
diagnostic.
If 9 flashes, the S2
serial port is
reporting a
diagnostic.
Possible causes
are:
If the port is
configured as a
Modbus or ELN
slave, the data
link layer is
reporting that at
least 75% of the
last characters
received have
had a failure
reported by the
UART or at least
75% of the last
messages
received have
been invalid.
If the port is
configured as a
Modbus Master,
at least 75% of
the last requests
to a particular
slave resulted in
no response or a
reply that failed
the data link
protocol.
1. ASYS and FSYS blocks HW
OK pins are turned off.
2. If configured as a Modbus
master:
ASYS and FSYS blocks
Modbus Master Fail pins
are turned on.
Slave and read blocks
associated with the slaves
experiencing the failure
have their read pins frozen
to the last value read.
Slave blocks associated
with the slaves
experiencing the failure
have their BAD COMM
and NO SCAN pins turned
on.
IN SCAN STATUS is set to
NO for all slaves
experiencing the failure.
COMM STATUS is set to
BAD for all slaves
experiencing the failure.
The slaves with the data
link errors have a non-zero
data link error count.
The slaves experiencing
the failure are moved to the
background scan rate.
1. Check baud rate
2. Check connectors
3. Check cable polarity
4. Isolate cabling from electrical
interference
5. If RS-232 to RS-485 converter
is used, check its power,
switch/jumper settings, and
polarity.
6. If configured as a Modbus
master, use the slave status
screens to determine which
slaves are experiencing the
problem. For those slaves
check:
Power
Connections
address
baud rate
parity
number of stop bits
for electrical interference
grounding
termination resistor (if at
end of link)
9. The diagnostic is cleared by
clearing the ports statistics.
2
The UART failed its
power-up tests
See above
Replace CPU module

Table of Contents

Related product manuals