Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 239
May 2019
4 Point Analog Output
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal block to allow mating with the module. See page 87.
Connect desired cable to AO module at controller. Choose from:
900RTC-L210 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L225 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
900RTC-L250 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
Install AO module label onto the module connector cover.
Connect shield drain wire to the grounding bars at the base of the ControlEdge HC900 rack. All
field-wiring shields must be grounded as described in the shield grounding section (page 83).
2
Mount RTP to DIN rail.
Latch to rail. See page 258.
Connect cable to RTP
3
Set/verify jumper positions as shown for use with an analog output module.
SW1 is not used. Module RIUP is not affected by using the RTP.
See page 246 for RTP internal schematic.
Jumper open
Jumper closed