ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP combines the two groups of 8 inputs into one group of 16.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 87.
Connect desired cable to 16 point AC DI module at controller. Choose from:
900RTC-H210 Remote Terminal High Voltage Cable assembly, 1.0 meters long
900RTC-H225 Remote Terminal High Voltage Cable assembly, 2.5 meters long
900RTC-H250 Remote Terminal High Voltage Cable assembly, 5.0 meters long
Install 16 point AC DI module label into module connector cover.
Connect shield drain wire to the grounding bars at the base of the ControlEdge HC900 rack. All
field-wiring shields must be grounded as described in the shield grounding section (page 83).