248 ControlEdge HC900 Process & Safety Controller User and Installation Manual Revision 10
May 2019
8 Point AC Digital Output
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: 8 point AC Output is limited to maximum of 2A per output for any VAC, 6A per RTP for
240VAC, 8A per RTP for 120VAC.
ATTENTION: The RTP combines the 8 isolated outputs into one group of 8.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 87.
Connect desired cable to 8 point AC DO module at controller. Choose from:
900RTC-H210 Remote Terminal High Voltage Cable assembly, 1.0 meters long
900RTC-H225 Remote Terminal High Voltage Cable assembly, 2.5 meters long
900RTC-H250 Remote Terminal High Voltage Cable assembly, 5.0 meters long
Install 8 point AC DO label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the ControlEdge HC900 rack. All
field-wiring shields must be grounded as described in the shield grounding section (page 83).
2
Mount RTP to DIN rail.
Latch to rail. See page 258.
Connect cable to RTP.
3
Set/verify jumper positions as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 85.
ATTENTION: SW1 only disconnects L1, not both sides of the AC powerline.
See page 246 for RTP internal schematic.
Jumper open
Jumper closed