ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: Mount RTP cable assembly to 900 Platform (Figure 109).
Remove appropriate key tabs from terminal block to allow mating with the module. See
ControlEdge or HC900 Hybrid Controller Installation and User guides for details.
Connect desired cable to 16 point UIO module at the IO Rack.
Choose from:
for modules with less than 2 Amps total
900RTC-L110, 900RTC-L210 Remote Terminal Cable Assembly, 1.0 meters long
900RTC-L125, 900RTC-L225 Remote Terminal Cable Assembly, 2.5 meters long
900RTC-L150, 900RTC-L250 Remote Terminal Cable Assembly, 5.0 meters long
for modules with more than 2 Amps total
900RTC-H110, 900RTC-H210 Remote Terminal Cable Assembly, 1.0 meters long
900RTC-H125, 900RTC-H225 Remote Terminal Cable Assembly, 2.5 meters long
900RTC-H150, 900RTC-H250 Remote Terminal Cable Assembly, 5.0 meters long
Install 16 point Safety Universal Input/ Output module insert into the module connector
cover.
Connect shield drain wire to the grounding bars at the base of the IO rack. All field-wiring shields
must be grounded as described in the shield grounding section of the ControlEdge or 900 Hybrid
Controller Installation and User guides.
Set/verify jumper positions as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 85.
ATTENTION: SW1 only is not used for this module.
See page 246 for RTP internal schematic.