254 ControlEdge HC900 Process & Safety Controller User and Installation Manual Revision 10
May 2019
16 Point Analog Output
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 87.
Connect terminal block end of desired cable assembly to 16 point Analog Output module at
controller. Choose from:
900RTC-3410 Remote Terminal Cable assembly, 1.0 meters long
900RTC-3425 Remote Terminal Cable assembly, 2.5 meters long
900RTC-3450 Remote Terminal Cable assembly, 5.0 meters long
Install 16 point Analog Output label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the ControlEdge HC900 rack.
All field-wiring shields must be grounded as described in the shield grounding section (page 83).
2
Mount RTPs to DIN rail.
Latch to rail. See page 258.
Connect cables to RTPs. Cables are marked “RTP A” and “RTP B.” In step 4, RTP A will be wired to
Inputs 1-10, RTP B to Inputs 9-16. You can write on the RTPs’ labels to distinguish them.
Note: Inputs 9 and 10 are wired between both RTPs.
3
Set/verify jumper positions on each RTP as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 85.
ATTENTION: SW1 opens the + side of the External 24V Power so that RIUP of module is possible.
See page 247 for RTP internal schematic.
Jumper open
Jumper closed