Revision 10 ControlEdge HC900 Process & Safety Controller User and Installation Manual 255
May 2019
16 Point Analog Output
Step
Action
4
Connect field wiring.
16 Point Analog Input
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP labeled “DI, DO, AO RTP ASSY” with jumpers J2-J9 is the correct one for 16
point AI.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 87.
Connect terminal block end of desired cable assembly to 16 point Analog Input module at controller.
Choose from:
900RTC-3410 Remote Terminal Cable assembly, 1.0 meters long
900RTC-3425 Remote Terminal Cable assembly, 2.5 meters long
Install 16 point Analog Input label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the ControlEdge HC900 rack.
All field-wiring shields must be grounded as described in the shield grounding section (page 83).
RTP A for
Outputs 1 to 8, 9+ and 10+
RTP B for
Outputs 11 to 16, 9- and 10-)
1 2 3 4 5 6 7 8 9
10
11
12
13
14
15 16 17
18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LOADS ARE 0 to 750 ohm
AO1+
AO1
-
AO2+
AO2
-
LOAD
AO-1
LOAD
AO-2
LOAD
AO-1
LOAD
AO-2
AO3+
AO3
-
AO4+
AO4
-
AO5+
AO5
-
AO6+
AO6
-
AO7+
AO7
-
AO8+
AO8
-
ETC.
1 2 3 4 5 6 7 8 9
10
11
12
13
14
15 16 17
18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
AO9
-
AO11+
AO10
-
AO12+
AO11
-
AO13+
AO12
-
AO14+
AO13
-
AO15+
AO14
-
AO16+
AO15
-
AO16
-
External 24VDC supply
DC+
SDC+
EXT 24V RTN
EXT +24V
AO10+
AO9+
Install 24V wires as shown:
22 to 10
22 to 12
24VRTN to 9
24VRTN to 11