258 ControlEdge HC900 Process & Safety Controller User and Installation Manual Revision 10
May 2019
32 Point DC Digital Output
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: 32 point DC Digital Output is limited to 6A per RTP and 0.5A per output.
Mount RTP cable assembly to ControlEdge HC900 Controller (Figure 109).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 87.
Connect terminal block end of desired cable assembly to 32 point Digital Output module at
controller. Choose from:
900RTC-3410 Remote Terminal Cable assembly, 1.0 meters long
900RTC-3425 Remote Terminal Cable assembly, 2.5 meters long
Install 32 point DC DO label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the ControlEdge HC900 rack.
All field-wiring shields must be grounded as described in the shield grounding section (page 83).
2
Mount RTPs to DIN rail.
Latch to rail. See page 258.
Connect cables to RTPs. Cables are marked “RTP A” and “RTP B.” In step 4, RTP A will be wired to
outputs 1-16, RTP B to outputs 17-32. You can write on the RTPs’ labels to distinguish them.
3
Set/verify jumper positions on each RTP as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 85.
ATTENTION: SW1 opens current loop on the ground side so that RIUP of module is possible, but
voltage is still present on the positive side at RTP and module terminals.
See page 256 for RTP internal schematic.
Jumper open
Jumper closed