BCU 460, BCU 465 · Edition 11.19 108
Parameters
11.14 Interface parameters
Interface parameters I040 to I099 are set at the fac-
tory and normally do not need to be adjusted. Chang-
ing the default settings of the interface parameters
will change the functions of the inputs at terminals 1
to41 and terminals 85 to90, see also from page21
(Connection diagram).
11.14.1 Flame control
Parameter I004
Parameter I004 = 0: flame control is performed with a
flame rod.
Parameter I004 = 1: flame control is performed with a
UV sensor for intermittent operation (UVS). For inter-
mittent operation, the operating state of the complete
system is limited to 24h pursuant to EN298. To meet
the requirement for intermittent operation, the burner
is shut down and restarted automatically after a con-
tinuous operating time of 24hours if it is not operated
in compliance with the standard. The restart does not
meet the requirements of EN298 for UV sensor con-
tinuous operation because the required self-test (at
least once per hour) is not performed while the burner
is operating. This shut-down and subsequent restart
are performed in the same way as a normal controlled
shut-down. Depending on the parameterization, the
burner is started with or without pre-purge. This pro-
cess is controlled independently by the BCU and there-
fore it must be checked whether the industrial process
permits the pause in heat supply it creates.
Parameter 04 = 2: flame control is performed with a UV
sensor for continuous operation (UVC).
The reaction times of the BCU and UV sensor for con-
tinuous operation are coordinated so that the set safety
time during operation (parameter A019) is not extend-
ed.