BCU 460, BCU 465 · Edition 11.19 112
Parameters
11.14.3 Function of terminal 64
Parameter I040
Terminal 64 can be assigned a function using param-
eter I040 depending on the power module LM..F1 or
LM..F3. Alternatively, the output can be actuated using
a bus system.
Parameter I040 = 0: Off. The output has no function.
Parameter I040 = 2: valve V5. Terminal 64 can be used
to activate a fifth valve. This option can only be selected
if power module LM..F3 is used.
Parameter I040 = 3: bus output 1. The output at termi-
nal64 can be actuated using a bus system. Can only be
selected with power module LM..F3.