BCU 460, BCU 465 · Edition 11.19 134
Technical data
Input voltage of signal inputs:
Rated value 120 VAC 230 VAC
Signal “1 80 – 132 V 160 – 253 V
Signal “0” 0 – 20 V 0 – 40 V
Signal input current:
Signal “1 max. 5 mA
Fuses, replaceable, F1/F2/F3: T 3.15A H,
pursuant to IEC 60127-2/5.
Does not meet the requirements for safety extra-low
voltage (SELV/PELV).
Ignition transformer
Burner
control unit
Ignition
transformer
(material No.)
Input Output
V AC Hz* A* V AC mA*
BCU..W1
TRS515PCISOH2
(34340585)
230 50 (60) 0.4 (0.3) 5000 15 (10)
BCU..Q1
TRS515PCISOH1
(34340581)
120 50 (60) 0.9 (0.6) 5000 15 (11)
BCU..W2
TRE820PISOH2
(34340586)
230 50 (60) 1.0 (0.7) 8000 20 (16)
BCU..Q2
TRE820PISOH1
(34340582)
120 50 (60) 1.9 (1.4) 8000 20 (16)
BCU..W3
TRS812PCISOH2
(34340587)
230 50 (60) 0.6 (0.4) 8000 12 (9)
BCU..Q3
TRS812PCISOH1
(34340583)
120 50 (60) 1.2 (0.9) 8000 12 (9)
BCU..W3
TRS820PISOH2
(34340587)
230 50 (60) 1.0 (0.7) 8000 20 (16)
BCU..Q3
TRS820PISOH1
(34340583)
120 50 (60) 1.7 (1.3) 8000 20 (16)
* Values in brackets apply to 60 Hz.
17. 2 Mechanical data
Weight: 5.5 kg.
Dimensions (W × H × D): 200 × 230 × 135 mm.
Connections:
Screw terminals:
nominal cross-section 0.2 mm²,
wire cross-section (rigid) min. 0.2 mm²,
wire cross-section (rigid) max. 2.5 mm²,
wire cross-section AWG/kcmil min.24,
wire cross-section AWG/kcmil max.12.
Spring force terminals:
nominal cross-section 2 x 1.5 mm²,
wire cross-section min. 0.2 mm²,
wire cross-section AWG min.24,
wire cross-section AWG max.16,
wire cross-section max. 1.5mm².