BCU 460, BCU 465 · Edition 11.19 132
BCM 400
Installation
Insert the bus module in the slot provided and set pa-
rameterA080.
16.5 Selection
Code Description
BCM Bus module
400 Series 400
S0
S1
Standard communication
SafetyLink
B1
B2
B3
PROFIBUS DP
1)
PROFINET
2)
EtherNet/IP
3)
/1
/3
9-pin D-Sub
Two RJ45 sockets
-0
-3
Three-point step control via bus
1)
Order No.: 74960690
2)
Order No.: 74960691
3)
Order No.: 74960692
16.6 Technical data
Electrical data
Power consumption: 1.2VA.
Power loss: 0.7 W.
Mechanical data
Dimensions (W × H × D):
96 × 63 × 23 mm (3.78 × 2.48 × 0.91 inch).
Weight: 0.3 kg.
Ambient conditions
Avoid direct sunlight or radiation from red-hot surfaces
on the unit.
Avoid corrosive influences, e.g. salty ambient air or SO
2
.
The unit may only be stored/installed in enclosed
rooms/buildings.
This unit is not suitable for cleaning with a high-pres-
sure cleaner and/or cleaning products.
Ambient temperature:
-20 to +70°C (-4 to +15F),
no condensation permitted.
Enclosure: IP 20 pursuant to IEC529.
Installation location: min. IP 65 (for installation in
BCU4xx).
Permitted operating altitude: < 2000 m AMSL.