BCU 460, BCU 465 · Edition 11.19 117
Replacement possibilities
12 Replacement possibilities
Burner control units BCU 460 and BCU 465 can be replaced by the next-generation devices BCU460 and
BCU465.
By comparison to the previous generation, the next-generation BCU4 units feature new technologies and func-
tions which can be freely parameterized.
Code Description of BCU (previous generation) Description of BCU Code
2)
BCU Burner control unit
Series 4 burner control unit BCU 4
4 Series 4
60
65
Standard version
Extended air control
Series 460
Series 465
60
65
3; 5; 10 Safety time on start-up t
SA
[s] Can be adjusted using parameter A094: 2 to 15 s
1; 2 Safety time during operation t
SB
[s] Can be adjusted using parameter A019: 0, 1, 2, 3, 4 s
L
1)
Air valve control
In conjunction with LM..F1 = with interface for IC40,
LM 400..F3 = with air valve control
5
1)
; 15
1)
;
25
1)
Low fire over-run time [s]
Can be adjusted using parameter A039 (Over-run time): 0 to
60 s
W
R
Mains voltage: 230 VAC, -15/+10%, 50/60 Hz
115 VAC, -15/+10%, 50/60 Hz
Mains voltage: 230 VAC, -15/+10%, 50/60 Hz
120 VAC, -15/+10%, 50/60 Hz
W
Q
1
1)
2
1)
3
1)
8
1)
Ignition transformer: TZI 5-15/100
TZI 7-25/20
T ZI 7,5-12/100
TZI 7,5-20/33
Ignition transformer: 5 kV, 15 mA, 100% duty cycle
8 kV, 20 mA, 19% duty cycle
8 kV, 12 mA, 100% duty cycle
8 kV, 20 mA, 33% duty cycle
1
2
3
8
GB
1)
Front film in English with additional stickers in D, F, I, NL, E Set of language stickers in GB, F, NL, I, E, see accessories
P
1)
Industrial plug connector
Flange plate: none
standard
M32
industrial plug connector, 16-pin
PROFIBUS
conduit
P0
P1
P2
P3
P6
P7
No valve proving system
With TC and POC valve proving system
With POC valve proving system
C0
C1
C2
D2
1)
D3
1)
High temperature operation in conjunction with: … UVS
… ionization or UVD
No high temperature operation
For high temperature operation
Flameless operation
D0
D1
D2

Table of Contents

Related product manuals