BCU 460, BCU 465 · Edition 11.19 109
Parameters
11.14.2 Air actuator
IC 40
Parameter I020 = 2: IC 40.
To ensure that the actuator IC40 can be operated on
the BCU..F1, parameter I020=2 (capacity control) must
be set. The operating mode of actuator IC40 may be
parameterized to11 or27.
BCU..F1
PE
L
N
N
28
L
58
37
N
27
L
57
36
N
29
L
59
38
F3 3,15 A
O
I
F1 3,15 A
82 81
80
95 96
97
51 21
BM
2322
85 86 87
92 91 90
54 24
N1
52 53
BM
55 25
N1
56 26
N1
E1
1
N1
N1
N1
N1
N1
230 V
UVS
3
1
2
4
6
5
7
40 41
35
39
E0
PE
IC 40
PE
19 18 16 15 14 12 11 10 87 54 21
A
AC
D
DC
M
mA
22 21 20
R..
66 67
64 6540
41
56 26
N1
90°
90°
The positions for maximum capacity and ignition
capacity can be set using the actuator. Terminal41
checks whether the position for maximum capacity has
been reached. Terminal40 checks the position for igni-
tion capacity. If the position is not reached within the
timeout time of 250s, a safety shut-down of the BCU
will be performed. A fault message (E A
, E A or E A ) will
be displayed, see page61 (Fault signalling).
If a controller enable is active, the control system is
enabled for operation via the outputs at terminals 65
and66.