BCU 460, BCU 465 · Edition 11.19 110
Parameters
Operating mode 11
Operating mode 11 allows cyclic operation (ON/OFF
and OFF/Low/High/OFF).
The actuator IC moves to the “High fire” position during
the controller enable procedure. There is no timeout ac-
tive in this case.
t [s]
t [s]
t
1
t
2
t
3
t
4
t
5
t
6
DI 1
DI 2
Purge
Closed
Ignition
High
fire
BCU IC40 (operating mode 11)
Signal at
terminal
Position Butterfly valve position
65 66
OFF OFF Closed Closed
ON OFF Ignition
Minimum/Ignition capacity
ON ON High-fire rate High-fire rate
OFF ON Purge Maximum capacity
Operating mode 27
During the controller enable procedure, the actuator
IC40 can be adjusted infinitely between the positions
for maximum and minimum capacity using its ana-
logue input (terminals18 and19). There is no timeout
active in this case.
t [s]
t [s]
t
1
t
2
t
3
t
4
t
5
t
6
0–20
mA
DI 1
DI 2
Purge
Closed
Ignition
BCU IC40 (operating mode 27)
Signal at
terminal
Position Butterfly valve position
65 66
OFF OFF Closed Closed
ON OFF Ignition
Minimum/Ignition capacity
ON ON 0 – 20 mA
Any position between minimum and
maximum capacity
OFF ON Purge Maximum capacity