Loading...
BCU 460, BCU 465 · Edition 11.19 69
Parameters
11.2 Interface parameters
Name Parameter Value range Description
Factory default
settings
Flame control I004
0
1
2
3
4
5
6
7
8
Ionization
UVS
UVC
Ionization control for burner 1 and UVS control for
burner 2
Ionization control for burner 1 and UVC control for
burner 2
UVS control for burner 1 and ionization control for
burner 2
UVS control for burner 1 and UVC control for burner 2
UVC control for burner 1 and ionization control for
burner 2
UVC control for burner 1 and UVS control for burner 2
0
Air actuator I020
0
2
5
Off
IC 40
Air valve
0
Function of terminal 64 I040*
0
2
3
Off
V5
Bus output 1
0
Contact 80, 81/82 function I050*
0
1
2
3
4
5
6
7
Off
Ready signal
Air signal
Purge signal
Cooling air valve
Flue gas valve
Fault signal
Burner 1 operating signal
6
Contact 90, 91/92 function I051*
0
1
2
3
4
5
6
7
Off
Ready signal
Air signal
Purge signal
Cooling air valve
Flue gas valve
Fault signal
Burner 1 operating signal
1