BCU 460, BCU 465 · Edition 11.19 70
Parameters
Name Parameter Value range Description
Factory default
settings
Function of contact 95/96 I052*
0
1
2
3
4
5
6
7
Off
Ready signal
Air signal
Purge signal
Cooling air valve
Flue gas valve
Fault signal
Burner 1 operating signal
7
Function of contact 95/97 I053*
0
1
2
3
4
5
6
7
Off
Ready signal
Air signal
Purge signal
Cooling air valve
Flue gas valve
Fault signal
Burner 1 operating signal
7
Contact 85/86, 87 function I054*
0
1
2
3
4
5
6
7
Off
Ready signal
Air signal
Purge signal
Cooling air valve
Flue gas valve
Fault signal
Burner 1 operating signal
2
Function of input 1 I061*
0
4
5
6
7
8
9
11
12
13
14
17
19
Off
Safety interlocks
Air
Cooling air
Air actuator R1
Air actuator R2
Start 1
Reset
Purge
LDS start-up conditions
High temperature operation
Flameless operation
Auxiliary gas
9
Function of input 2 I062* See I061 See I061 11