BCU 460, BCU 465 · Edition 11.19 71
Parameters
Name Parameter Value range Description
Factory default
settings
Function of input 3 I063* See I061 See I061 12
Function of input 4 I064* See I061 See I061 5
Function of input 5 I065* See I061 See I061 0
Function of input 6 I066* See I061 See I061 14
Function of input 7 I067* See I061 See I061 0
Function of input 35 I068* See I061 See I061 4
Function of input 36 I069*
0
1
2
3
4
5
6
7
8
9
11
12
13
14
17
19
Off
Sensor 1
Sensor 2
Sensor 3
Safety interlocks
Air
Cooling air
Air actuator R1
Air actuator R2
Start 1
Reset
Purge
LDS start-up conditions
High temperature operation
Flameless operation
Auxiliary gas
0
(on BCU 460)
1
(on BCU 465)
Function of input 37 I070* See I069 See I069
0
(on BCU 460)
2
(on BCU 465)
Function of input 38 I071* See I069 See I069
0
(on BCU 460)
3
(on BCU 465)
Function of input 39 I072* See I061 See I061 13
Function of input 40 I073* See I061 See I061 7
Function of input 41 I074* See I061 See I061 8
* Interface parameters I040 to I099 are set at the factory and normally do not need to be adjusted.