BCU 460, BCU 465 · Edition 11.19 67
Parameters
Name Parameter Value range Description
Factory default
settings
High temperature operation (bus) A088
0
1
2
5
Off
Via fail-safe bus (K-SafetyLink)
Via terminal
Via fail-safe bus (K-SafetyLink) and terminal
2
LDS (bus) A089
0
1
2
5
Off
Via fail-safe bus (K-SafetyLink)
Via terminal
Via fail-safe bus (K-SafetyLink) and terminal
2
Safety time 1 tSA1 A094 2 – 15 s Time in seconds
Function of sensor 1 A101
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
32
33
34
35
48
49
50
51
52
53
54
55
56
No function
APS Purge
APS Stage 1
APS Purge & Stage 1
APS Stage 2
APS Purge & Stage 2
APS Stage 1 & Stage 2
APS Purge & Stage1 & Stage2
APS Flameless
APS Purge & Flameless
APS Stage 1 & Flameless
APS Purge&Stage1&Flameless
APS Stage 2 & Flameless
APS Purge&Stage2&Flameless
APS Stage 1&2 & Flameless
APS Purge & Stage1&2 & Flameless
APS External Low
APS External Low & Purge
APS External High
APS External High & Purge
POC V1
POC V2
POC V3
POC V4
POC V5
TC
GPS Flame mode
GPS Flameless operation
GPS Operation
0
Function of sensor 2 A102 See A101 See A101 0
Function of sensor 3 A103 See A101 See A101 0