Getting Started
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 101
Refer to the parameters and configuration options in LAN tab under
LAN A port given in section 3.2.10.1 for more information.
3. Click the Secondary LAN Port tab to view the Property.
You can view or edit this property.
Communication fail delay When a field communication fail occurs it is possible to
maintain last valid scan data in the CIU 888 database
during a configurable amount of time.
Minimum time to mask a field communication fail: 0 sec
(delay mechanism disabled).
Maximum time to mask a
Data fail delay When a field data fail occurs it is possible to maintain
last valid scan data in the CIU 888 database during a
configurable amount of time.
Minimum time to mask a field data fail: 0 sec (delay
mechanism disabled).
Maximum time to mask a field data fail:
OPC UA server enable This setting would enable / disable the OPC UA Server
on the CIU 888's ethernet port (LAN).
0 - OPC UA server is disabled
1 - OPC UA server is enabled
Server URL This setting depicts the server URL. The OPC UA cli-
ents to CIU 888 using this URL. The URL shall be in the
below format.
opc.tcp://192.168.20.10:51000
Default value: Empty string
Parameter Configuration option
Secondary IP Address In case of redundant CIUs, this indicates the IP address
of the corresponding Ethernet port in the partner CIU.
Format: w.x.y.z
Example: 10.70.100.102
Parameters Configuration options