STRYKER CVAHU ZIO CONFIGURATION GUIDE
23
Figure 21: Parameter Status Trmnl Ld
TRMNL LD: Displays effective terminal load (%) on
the controller. Its value ranges from 160% to 160%. A
positive value indicates a cooling load and a negative
value indicate heating load.
Figure 22: Parameter Status Aux Econ
AUX ECON: Displays auxiliary economizer status as
ON or OFF
Configuration settings in program are as follows:
0 = OFF, 1 = ON, 255 = UNDEFINED
Figure 23: Parameter Status Free Mod
FREE MOD: Displays configured free modulating1
(%) output signal. Its value ranges from 0% to 100%.
It is controlled by network command.
Figure 24: Parameter Status Free Dtg
FREE DTG: Displays configured free digital1
command status as ON or OFF. It is controlled by
network command.
Configuration settings in program are as follows:
0 = OFF, 1 = ON, 255 = UNDEFINED