STRYKER CVAHU ZIO CONFIGURATION GUIDE
47
Figure 84: Parameter Cnfg Out Clg Stg3
CLG STG3: Displays and allows modification of
logical output configuration /terminal assignment for
Cooling or Heat Pump stage 3 Command. This can
be changed as AO 1, AO 2, DOC1, DOA1, DOA2,
DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and
UNDEFINED.
Default Parameter setting: UNDEFINED
Configuration settings in program are as follows:
0 = AO 1
1 = AO 2
2 = DOC1 (DO1)
3 = DOA1 (DO2)
4 = DOA2 (DO3)
5 = DOA3 (DO4)
6 = DOB1 (DO5)
7 = DOB2 (DO6)
8 = DOB3 (DO7)
9 = DOB4 (DO8)
10 = AO 3
255 = UNDEFINED
Figure 85: Parameter Cnfg Out Hp Chang
HP CHANG: Displays and allows modification of
logical output configuration /terminal assignment Heat
Pump change over relay command. This can be
changed as AO 1, AO 2, DOC1, DOA1, DOA2,
DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and
UNDEFINED.
Default Parameter setting: UNDEFINED
Configuration settings in program are as follows:
0 = AO 1
1 = AO 2
2 = DOC1 (DO1)
3 = DOA1 (DO2)
4 = DOA2 (DO3)
5 = DOA3 (DO4)
6 = DOB1 (DO5)
7 = DOB2 (DO6)
8 = DOB3 (DO7)
9 = DOB4 (DO8)
10 = AO 3
255 = UNDEFINED