STRYKER CVAHU ZIO CONFIGURATION GUIDE
48
Figure 86: Parameter Cnfg Out Htg Stg1
HTG STG1: Displays and allows modification of
logical output configuration /terminal assignment for
Heating stage 1 Command. This can be changed as
AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1,
DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED
Configuration settings in program are as follows:
0 = AO 1
1 = AO 2
2 = DOC1 (DO1)
3 = DOA1 (DO2)
4 = DOA2 (DO3)
5 = DOA3 (DO4)
6 = DOB1 (DO5)
7 = DOB2 (DO6)
8 = DOB3 (DO7)
9 = DOB4 (DO8)
10 = AO 3
255 = UNDEFINED
Figure 87: Parameter Cnfg Out Htg Stg2
HTG STG2: Displays and allows modification of
logical output configuration /terminal assignment for
Heating stage 2 Command. This can be changed as
AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1,
DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED
Configuration settings in program are as follows:
0 = AO 1
1 = AO 2
2 = DOC1 (DO1)
3 = DOA1 (DO2)
4 = DOA2 (DO3)
5 = DOA3 (DO4)
6 = DOB1 (DO5)
7 = DOB2 (DO6)
8 = DOB3 (DO7)
9 = DOB4 (DO8)
10 = AO 3
255 = UNDEFINED