STRYKER CVAHU ZIO CONFIGURATION GUIDE
37
Figure 65: Parameter Cnfg Ctl Htg Tr
HTG TR: Displays and allows modification of space
heating PID control throttling range. Its value ranges
from 0 to 30 ∆F.
Throttling Range (TR):
When TR is nonzero, this value of TR is used by the
space heating PID control.
Auto Gain Selection:
When TR is 0, Table 7 shows the TR values are used
by the space heating PID control.
Table 7: TR values used by the space heating pid
control.
Type
TR
1stg
3
2stg
5
3stg
7
4stg
8
Figure 66: Parameter Cnfg Ctl Htg It
HTG IT: Displays and allows modification of heating
PID control integral time. Its value ranges from 0 to
5000 sec.
Integral Time (IT):
When TR is nonzero, this value of IT is used by the
space heating PID control.
Auto Gain Selection:
When TR is 0, Table 8 shows the IT values are used
by the space heating PID control.
Table 8: IT values used by the space heating pid
control.
Type
IT
1stg
3333
2stg
2000
3stg
1429
4stg
1111