FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
19
Control Panel Terminal Blocks Wiring Requirements
2.4.6 ES-50X
TB11 provides two types of 24 VDC power; Nonresettable and Resettable, user programmable.
TB12 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
2.4.7 ES-200X
TB11 provides two types of 24 VDC power; Nonresettable and Resettable, user programmable. PWR1 has a user programmable Class A
wiring option.
TB12 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
TB12
SLC
RTN RTN
24VDC
TB11
SLC Out
SLC-es50tb.wmf
SLC Return
Figure 2.11 ES-50X Terminal Block
Resettable or Nonresettable Power-
user programmable
TB12
SLC
RTN RTN
PWR1 PWR2
TB11
SLC Out
Resettable or Nonresettable Power-
user programmable
Resettable or Nonresettable Power, Class A optional, user programmable
SLC-es200tb.wmf
SLC Return
Figure 2.12 ES-200X Terminal Blocks