Section 8: Multiple Input/Output Modules
8.1 Description
The CDRM-300 is an addressable module that functions as two individual relay control modules (two isolated sets of Form-C relay con-
tacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:
8.2 CDRM-300 Installation & Wiring
8.2.1 Setting an SLC address for a CDRM-300 Module
Each module is factory preset with an address of “00”. To set an SLC address, use a screwdriver to adjust the rotary switches on the mod-
ule to the desired address. Each module can use up to four (4) addresses. The base address selected via the rotary address switches will
be assigned to relay output #1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to monitored
input #1, relay output #2, and monitored input #2.
8.2.2 Wiring a CDRM-300 Module (Form-C Relay)
The figure below shows a CDRM-300 module wired to the Control Panel.
Load Description Application
Maximum
Voltage
Current
Rating
Inductive (PF = 0.35) Non-Coded 25 VAC 2.0 A
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Inductive (L/R = 20ms) Non-Coded 30 VDC 0.46 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Resistive Non-Coded 125 VDC 0.9 A
Inductive (PF = 0.75) Non-Coded 125 VAC 0.5 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.3 A
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
SLC
fdrm-1.wmf
CDRM-300
IDC 1 (+)
IDC 1 (-)
IDC 2 (+)
IDC 2 (-)
NC
C
NO
NC
C
NO
Figure 8.1 CDRM-300 Wiring Connections
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open