EasyManua.ls Logo

Honeywell Fire-Lite Alarms MS-9600UDLS - 3: MMF-300 Wiring for Emergency Alarm System Applications

Honeywell Fire-Lite Alarms MS-9600UDLS
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
FireLite SLC Wiring Manual P/N 51309:R3 7/29/2019
Monitor Modules MMF-300 Wiring Diagrams
5.3.3 MMF-300 Wiring for Emergency Alarm System Applications
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting
an SLC address for a Single Point Module” on page 33.
The figure below shows typical wiring for a supervised and power-limited Emergency Signaling circuit using an MMF-300 module.
See “Power Considerations” on page 63 for information on supervising 24 VDC power.
See Section 6, “Control Modules” for instructions on using control modules as NACs on an SLC.
Refer to the Device Compatibility Document #15384 for compatible smoke detector
s.
+
+
-
-
47K ELR
(supplied
with module)
SLC
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
IDC
UL-listed Signaling
appliance such as the
Fire-Lite FSS-2400E
SLC-emer.wmf
Figure 5.11 Emergency Signaling Wiring with an MMF-300

Table of Contents

Other manuals for Honeywell Fire-Lite Alarms MS-9600UDLS

Related product manuals