FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
41
MMF-302 Wiring Diagrams Monitor Modules
5.6.2 Wiring a NFPA Class A IDC with an MMF-302
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting
an SLC address for a Single Point Module” on page 33.
The figure below shows typical wiring for a supervised and power-limited NFPA Class A IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by th
e
module.
See “Power Considerations” on page 63 for information on 24 VDC power.
SLC
Two-wire
smoke
detectors
3.9K ELR
(supplied with module)
IDC
MMF-302
SLC-idcD2tpH.wmf
24 VDC Resettable power.
90 mA External 24 volt supply required
Figure 5.16 Typical Class A IDC Wiring with an MMF-302