FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
47
CMF-300-6 Installation Control Modules
6.4.7 Circuit Board Information
CMF-300-6.wmf
Synchronization Generator -
Not Supported. DO NOT
remove shunts.
Power Supply Monitors -
Not Supported. DO NOT
remove shunts.
Disable Address -
Place shunt onto required pins.
Select
Class B or
Class A -
Remove shunt for Class A.
Short Circuit Protection - Remove
shunt from the corresponding pins to
enable. Shunt #1 for first address, #2
for second address, etc.
#1 #2 #3 #4 #5 #6
SLC Address
Set rotary switches to
address required.
Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.
Figure 6.4 CMF-300-6 Control Module Settings