FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
75
Appendix E: Canadian Versions of SLC Devices
UL-listed SLC Device ULC-listed SLC Device Description
Detectors
AD350, AD355, AD365,
AD365-IV
AD350A, AD355A,
AD365A, AD365A-IV
Intelligent detector that combines a photoelectric sensing chamber and fixed temperature heat
detection (135°F/57.2°C).
CP350, CP355 CP350A, CP-355A Addressable, intelligent smoke detector that incorporates an ionization sensing chamber.
Designed to provide open area protection.
SD350,SD355,
SD355R, SD365(-IV),
SD365R(-IV)
SD350A, SD355A,
SD355RA, SD365A(-
IV), SD365RA(-IV)
Addressable intelligent smoke detector that uses a photoelectric sensing chamber. Listed for use
in ducts. Designed to provide open area protection.
(-IV in model number indicates ivory color.)
SD350T, SD355T,
SD365T(-IV)
SD350TA, SD355TA,
SD365TA(-IV)
Adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C).
(-IV in model number indicates ivory color.)
SD355CO, SD365CO NA Addressable detector that provides both fire and carbon monoxide (CO) detection.
H350, H355, H365(-IV) H350A, H355A,
H365A(-IV)
Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection
with 50 foot spacing capability. A fixed temperature sensor with 135°F fixed temperature alarm.
(-IV in model number indicates ivory color.)
H350R, H355R,
H365R(-IV)
H350RA, H355RA,
H365RA(-IV)
Incorporates a thermal rate of rise of 15°F (9.4°C).
(-IV in model number indicates ivory color.)
H355HT, H365HT(-IV) H355HTA, H365HTA(-
IV)
High temperature sensor with 190°F (87.8°C) fixed temperature alarm.
(-IV in model number indicates ivory color.)
OSI-RI-FL N/A Addressable long range projected beam smoke detector designed to provide open area
protection.
D355PL, D365PL D355PLA, D365PLA An addressable non-relay photoelectric low flow smoke detector.
DNR DNRA Photoelectric Duct Detector, Low-flow. Requires SD350(A), SD355(A), or SD365(A) detector.
Bases
B210LP B210LPA Standard U.S. Low-Profile base (6", 15.24 cm).
B501(-WHITE, -BL, -IV) B501(-WHITE, -BL, -IV) Standard European flangeless base (4", 10.16 cm)
(-IV in model number indicates ivory color. -BL in model number indicates black color).
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includes Sounder base with temporal sounder (UL 8th Edition).
B501BH-2, B501BHT-2 N/A Sounder base, includes Sounder base with temporal sounder (UL 9th Edition).
B224RB, B224RB-WH,
B224RB-IV
B224RBA, B224RBA-
WH, B224RBA-IV
Low Profile Intelligent relay base.
B224BI, B224BI-WH,
B224BI-IV
B224BIA, B224BIA-WH,
B224BIA-IV
Low Profile Intelligent isolator base.
B200S-WH
B200S-IV
B200SA-WH,
B200SA-IV
Intelligent sounder base, programmable, temporal or steady.
B200S-LF-WH,
B200S-LF-IV
N/A Intelligent sounder base, programmable, for low frequency applications
B200SR-WH
B200SR-IV
B200SRA-WH,
B200SRA-IV
Intelligent sounder base, temporal or steady.
B200SR-LF-WH,
B200SR-LF-IV
N/A Intelligent sounder base for low frequency applications
B300-6(-IV) B300A-6(-IV) Standard U.S. Low-Profile base (6", 15.24 cm). (-IV in model number indicates ivory color.)
Monitor and Zone Interface Modules
MMF-300 MMF-300A Used for normally open contact alarm initiating devices, such as manual pull stations, four-wire
smoke detectors, heat detectors, waterflow, and supervisory devices.
MMF-302 MMF-302A Used to interface with two-wire smoke detectors in addition to normally open contacts.
MDF-300 MDF-300A Two independent 2-wire Initiating Device Circuits (IDCs) at two separate, consecutive addresses.
Wire supervised IDCs as NFPA Class B or Class A circuits. The modules come with a
thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
MMF-301 MMF-301A Functionally similar to the MMF-300(A) Monitor Module, but offered in a smaller package for
mounting directly in the electrical box of the device being monitored. (Class B input circuit only.)
BG-12LX BG-12LX An addressable manual pull station with key-lock reset feature. The addressable module is
housed within the pull station.
Control Modules
CMF-300 CMF-300A Control Module, NAC: Addressable Control Module used as Notification Appliance Circuits
(NACs) to power and supervise compatible, UL-listed notification appliances. Wired supervised
NACs as NFPA Class B or Class A. The modules come with a thermoplastic cover for mounting
to a 4-inch (10.16 cm) square mounting box.
CRF-300 CRF-300A Relay Control Module is similar to the CMF-300(A) except used as a Form-C control relay
module.
Fault Isolator Module