FireLite SLC Wiring Manual P/N 51309:R3 7/29/2019
Terminal Conversion Charts for New & Legacy Devices MMF-300
C.3 MMF-300
Legacy Module Terminal Number
(V-Type)
Terminal Function
Newer Module Terminal Number
(H-Type)
1SLC - 1
2SLC + 2
3VDC -11
4 VDC + 10
5Unused 5
6 Solenoid B/A - 6
7 Solenoid B/A + 7
8 Solenoid A + 8
9 Solenoid A - 9
N/A Unused 3
N/A Unused 4
Table C.2 CMF-300 and MMF-302 Terminal Conversions
Newer Module
(H-Type)
Class A Supervision -
Class A Supervision+
Class A/B Supervision +
SLC -
SLC +
SLC -
SLC +
Class A Supervision -
Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
Legacy Module
(V-Type)
Legacy Module Terminal Number
(V-Type)
Terminal Function
Newer Module Terminal Number
(H-Type)
1SLC - 1
2SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
6 Class A/B Supervision - 6
7 Class A/B Supervision + 7
8 Class A Supervision + 8
9 Class A Supervision - 9
N/A Unused 10
N/A Unused 11
Table C.3 MMF-300 Terminal Conversions