EasyManua.ls Logo

Honeywell Fire-Lite Alarms MS-9600UDLS - MMF-300 Wiring Diagrams; 1: Wiring a NFPA Class B IDC with an MMF-300

Honeywell Fire-Lite Alarms MS-9600UDLS
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
FireLite SLC Wiring Manual P/N 51309:R3 7/29/2019
Monitor Modules MMF-300 Wiring Diagrams
5.3 MMF-300 Wiring Diagrams
Following are wiring diagrams that depict NFPA Class B and Class A Initiating Device Circuits (IDCs) using MMF-300 monitor mod-
ules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamperes @ 24 VDC (nominal).
5.3.1 Wiring a NFPA Class B IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting
an SLC address for a Single Point Module” on page 33.
The figure below shows typical wiring for a supervised and power-limited NFPA Class B IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 63 for information on supervising 24 VDC power.
47K ELR
(supplied
with module)
Heat
detector
SLC
MMF-300
IDC
24 VDC Power
Filtered, Regulated,
Resettable
24 VDC
Four-wire
Detector Base
Manual pull
station
From Supply
To Next IDC
or
Supervision Device
SLC-idcB1tpH.wmf
Figure 5.9 Typical Class B IDC Wiring with an MMF-300

Table of Contents

Other manuals for Honeywell Fire-Lite Alarms MS-9600UDLS

Related product manuals