Sounders Configuration
¨
The standard alarm sounders of each standalone system can be configured for three sound output signals.
¨
every 250mS over a 2 second time the sound output can be altered to high, low or off tone.
¨
sound signal configuration can be altered by modifying the FAB-SAB pairs by pressing the button Menu On/Off
to select [Set-Up] -> <etc-> -> [Modify]-> <etc> -> [Signal n] -> [Sounder] -> [Enter] and enter the FAB/SAB
for signal n and press enter.
FABs & SABs
The FAB (first action byte) determines tone and On/Off control while the SAB (second action byte) determines the action to be
performed on the output.
Number FAB action SAB action
0 no output
Turns Off selected Outputs
1 - 10mS pulse on Selected Outputs
2 frequency tone 40mS pulse on Selected Outputs
3 - 90mS pulse on Selected Outputs
4
On/Off control.(On
being low frequency)
160mS pulse on Selected Outputs
5 - 250mS pulse on Selected Outputs
6 high frequency tone 350mS pulse on Selected Outputs
7 - 480mS pulse on Selected Outputs
8 - 630mS pulse on Selected Outputs
9 - 800mS pulse on Selected Outputs
A - 980mS pulse on Selected Outputs
B - 1.2S pulse on Selected Outputs
C - 1.4S pulse on Selected Outputs
D - 1.6S pulse on Selected Outputs
E 1.9S pulse on Selected Outputs
F Turn on Selected Outputs
Factory Default FABs SABs
Time in seconds
0 0.25 0.5 0.75 1.0 1.25 1.5 1.75
Signal 3 (Continuous)
Output turns on Low frequency sound continuous
every 0.5 seconds.
4F 00 4F 00 4F 00 4F 00
Signal 2 (Evacuate)
First output turns on Low frequency sound
continuously, then every half second the High
frequency output is pulsed for 250mS.
4F 25 4F 25 4F 25 4F 25
Signal 1 (Alert)
Pulses high frequency for 250mS every half second.
65 00 65 00 65 00 65 00
Generic Commissioning instructions
124 4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Appendix C - Guidelines for standalone system