Checking device status
To list the status of a device on an allocated loop at the Control
Panel: Press Menu On/Off button and then select [Info],
momentarily press <etc> to select [Status] -> [Device], enter a
device number, select [Loop], enter the loop number n, select
[Enter] to view device status information.
0 - Output, I - Input and . signifies not used
Device digitalI/0 channels
S cubed 0000
1- IR control
2 - Tone
3 - Power
4 - Strobe
5
Sounder .00.
3 - Low freq.
2 - On/Off
Repeat sounder . 0 0 .
Interface unit (mains
powered)
all possible
I - input
0 - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5-battery
6-mains
Optical . . . 0 1
Optical heat . . . 0 1,2
Heat . . . 0 4
Slave Relay 0 . . 0+R
Slave LED . . . 0 +L
Beam transmitter . . . 0 2
Beam receiver . . . 0 1- raw data
2- average
data
MCP . . . 0 6
Repeat panel . . . 0 -
Zonal mimic . . . 0 -
Device digitalI/0 channels
Mimic panel
(standard A2 and A4
size)
...0 -
Loop interface all possible
I - input
0 - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5
Single channel
interface unit
I0.0 1,2,5
Loop powered zone
module
I..0 1,5
Optical/Heat
Sounder
.000 1,2
T-breaker O/S . . . 0
S-Quads
S-Quad Heat Sensor . . . 0 2
S-Quad Heat Sensor
Sounder
.000 2,5
S-Quad Dual Optical
Heat Sensor
. . . 0 1, 2,4
S-Quad Dual Optical
Heat Sensor Strobe
0..0 1,2,4,5
S-Quad Dual Optical
Heat Sensor
Sounder
.000 1,2,4,5
S-Quad Dual Optical
Heat Sensor Speech
Strobe
0000 1,2,4,5
S-Quad Dual Optical
Heat Sensor CO
...0 1,2,3,4,5
S-Quad Dual Optical
Heat Sensor CO
Speech Strobe
0000 1,2,3,4,5
+ Monitored input 6
+ Monitored output 6
Analogue Channel 1 is forward scatter optical smoke sensor
Analogue Channel 2 is heat sensor
Analogue Channel 3 is for CO gas sensor
Analogue Channel 4 is for backward scatter optical smoke
sensor
Analogue Channel 5 reports sounder/flasher/speech faults to
the control panel
Analogue Channel 6 reports monitored input/monitored output
faults/operation to the control panel
"
The correct device type may not be displayed
if the loop circuit has allocation faults.
¨
Check that the device is of the correct type and is
suitable for the area in which it is installed.
¨
Check the digital status of all devices.
¨
On successful allocation check that the total number of
devices found equals the number installed. Also there
will be a loop voltage on the unconnected end of the
cable.
Generic Commissioning instructions
50 4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Checking device status
Loop 1 No. 7 Dual optical/Heat/CO
LB1:C End1:Hi End2:Hi
I/O:...0 Anal:1-4
2nd:250 3rd:0 Short delay:0
Zone 1 Zone 1
LED)
,6
Loop on which
the device is installed
Location of the
device on the loop
Device description
Description of
monitored input/LED
attached to the device
Loop breaker
condition
C:closed
Status of End 1
of the device
(high or low)
Status of End
2
of the device
(high or low)
Digital
Input outputs
Analogue channels
used
1:Optical (forward)
2:Heat
3:Gas
4:Optical (Backward)
5:Sounder/Strobe/Speech fault
6:Monitored line or LED
Secondary address
denotes group of devices
Tertiary address
used primarily by
sounders/strobe
Short circuit delay
associated with
number of T breakers
off T breakers
Zone number and label