Honeywell Gent Viglion EN54 - How to Check Network Card Status; Fault Finding; High Errors

Honeywell Gent Viglion EN54
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
How to check Network Card status
Using the Menu On/Off -> [Info] -> [Status] -> [Card] and enter the network card 10. The display will confirm:
¨
address of the network card
¨
address of network controller
¨
and a set of condition codes
Errors meaning
Parity Parity is incorrect, data corrupted.
Framing 8- bit transmitted incorrectly and the data line does not return to logic 1 at the end of the transmission.
CRC Cyclic redundancy code. When a message consisting of a number of 8 bit transmissions is sent, a calculation is
carried out to check that data corruption has not occurred.
Time out
error
Where an 8 bit transmission block is not fully received, the network card will time out ready to receive the next
message. Time out error will also be generated for each parity/ framing error.
Freeblock Free memory blocks available to temporarily store messages waiting to be processed. The maximum number =
199, although it may drop as low as 175 - 180 on a highly populated network. A lower value may indicate a high
error value and will require rectification.
Fault Finding
¨
The communication path in a secure network alternates between end 1 (side 1) and end 2 (side 2) every minute.
¨
The network will be non secure until the last panel is connected and powered-up.
High errors
¨
Check cable lengths and type used.
¨
Check wiring, connections and earthing arrangements.
¨
Replace network card at point of failure.
¨
Check the addresses and baud rates of the input output and network cards of the networked panels.
¨
Check the network cable is correctly earthed to the equipment.
¨
It may be necessary escalate an investigation to:
look at the noise voltage between conductors, screen and earth.
"
Always reset the Network Card first when rechecking for errors, using [Test/Eng] -> [Card] ->[Reset] ->
Network Card 10.
The networked system may now be configured for network commands to be actioned, such as master sectors and global alarms as
per site requirement.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms. 69
Vigilon (EN & BS) Compact (VA) panels
Vigilon Compact Network
Card 10 Is OK Fault 0:Disable 0:Warning 0
Address (0) Version 4.06 5/7/06
Node 3 Controller 1 Baud Rate 38400
Condition00000021198199
Side 2
Parity/
Framing
error
Side 1
Parity/
Framing
error
Side 2
CRC
Side 1
CRC
Side 2 Side 1
End
communicating
1or2
Freeblock
Check
software
1 error = count of
10 but every 1sec
the counter is
decremented by 1
Current
message
errors
1error=
count of
100
Timing
errors
UART
type
0-Rckwell
1-Phillips
2-Phillips SMT
Only appears
on Controller