S-Quad
¨
The sensor(s) part of the S-Quad must be system
tested, see Testing fire sensors.
¨
For the Sound and Speech part of the S-Quad ensure
each device outputs the correct signal at the
appropriate volume level and ensure the strobe
operates at the required flash rate. All S-Quad devices
in the system should have been setup using the
commissioning tool.
¨
Each S-Quad should be tested for correct operation in
the event of fire.
¨
The sound levels in the areas should be tested in
accordance with the British Standard requirements and
to meet the site specific needs as agreed with the
customer.
Sounders
¨
With the standard alarm sounder it is possible to lower
sound levels by shorting link P3 across pins 2-3
(adjust). This enables the sound output to be varied
using RV3.
"
The sensor sounder and repeat sounder
devices have no sound level adjustment. The sensor
sounder has a blue band running around the central outer
moulding to ease identification.
¨
Each sounder should be tested for correct operation in
the event of fire.
¨
The sound levels in the areas should be tested in
accordance with the British Standard requirements and
to meet the site specific needs as agreed with the
customer.
Auxiliary equipment
"
Prior to any functional tests on the system, all
auxiliary equipment should be isolated.
Tests
¨
Tests should be carried out following customer
consent. It may also be necessary to obtain third party
consent depending on the equipment connected to the
auxiliary contacts.
¨
All these tests on auxiliary equipment should be as
agreed during the project design stage.
Repeat panel
Each repeat panel should be tested for the following:
¨
Cancel Buzzer
¨
System event messages and indications
¨
Display of active event log
Mimic Panel
Each Mimic Indicator should be configured and tested for the
following:
¨
To confirm fires are indicated
"
1. The power to an A4 mimic display is supplied from the
connected A4 mimic control unit.
2. The fire/fault buzzer in an A4 mimic panel will not
operate if it is disabled. However the panel does provide
common light indication of fire and fault event.
¨
Battery disconnection
¨
Mains supply disconnection
Lamp Test
¨
On an A2 mimic panel is performed by using a test
key.
¨
On an A4 mimic panel is performed by inserting a
2mm pin like object (for example a small terminal
screwdriver) into a hole located on the underside of the
panel enclosure.
Deviations from standards
¨
The results of system tests carried out must be in
accordance with the relevant standards and project
specification.
¨ Any deviations must be documented and reported for
approval.