Wiring of external circuits
¨
With the exception of the mains cable, ensure the
following external circuit cables are left disconnected
at this stage of commissioning:
•
loop circuits
•
clean contacts
•
auxiliary circuits
•
master alarms (the end-of-line resistor (10K Ohm)
should be fitted to inhibit a master alarm circuit
fault indication).
•
Monitored input (the end-of-line resistor (10K
Ohm) should be fitted to inhibit a monitored input
fault indication).
&
Ensure the mains cable is securely
connected to the mains terminal block on the Power
supply unit (PSU).