EasyManua.ls Logo

Honeywell Gent Viglion EN54 - Device Checks; Checking the Time Averages

Honeywell Gent Viglion EN54
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device checks
"
Ensure all dust covers have been removed from the sensor heads and the system is allowed to operate for at
least 24 hours to obtain accurate time average and condition code readings.
Checking the time averages
You can manually recover card data. The following
procedure assumes there is no password access
required. Press the Menu On/Off button and then
[Info], momentarily press <etc> to select [Time
Avg] and type in the channel number from the
range 1-6, select [Device] and type in the device
number for which the time average is required,
select [Loop] and type in the loop number of the
device ->[Enter]. The display shows time averages for the device.
Foreground (fast) time average readings Background (slow) time average readings
Tnew T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
On
demand
80mS 320mS 1.28S 5.12S 20.48S 1.36min 5.46min 21.84min 1.45hr 5.82hr 23.3hr
Normally reads 252, unless there is a
threshold.
Device type 34K Analogue Channel
number
Time average
Tnew
Optical
Heat
1
2
200 - 235
180 - 210
Heat
180 - 210
Beam Transmit
0
Beam Receive 2
150 - 170
Device type S-Quad Analogue Channels Time average Tnew
Heat Sensor 2 - heat 66
Heat Sensor Sounder 2 - heat 66
Dual Optical Heat Sensor 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Strobe 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Sounder 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Speech Strobe 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor CO 1 - optical (forward)
2 - heat
3-CO
4 - optical (backward)
25
66
25
40
Dual Optical Heat Sensor CO Speech Strobe 1 - optical (forward)
2 - heat
3-CO
4 - optical (backward)
25
66
25
40
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms. 51
Vigilon (EN & BS) Compact (VA) panels
Device checks
Average Channel 1 Device 1 Loop 1
19 252 252 252 252 252 19 19 19 19 18 18
Time average readings of Channel 1 device 1 loop 1
23:15
Tnew (On demand)
Background (slow) Time
average readings T6 of T11
Channel 1 Device 1 loo
p
1
Foreground (fast) Time
average readings T1 to T5 of
Channel 1 Device 1 loop 1
e Aver channel 1 Device 1 Loop 1
[Repeat] [Previous] [Next] [Cancel]

Table of Contents

Related product manuals