Wiring a Copper network
Wiring a Fibre network
Single network without domain bridge
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms. 71
Vigilon (EN & BS) Compact (VA) panels
Single Vigilon Network
C
8
7654321
BACKPLANE
Control Panel
Side 1
(End 1)
P7
Rx
P4
Tx
P6
Rx
P5
Tx
P3
P2
Links P2 and P3 are booster links.
Normally the links are not fitted, however for
distance exceeding 750m the links must be fitted.
Rx
Tx
C
8
7654321
BACKPLANE
Control Panel
P7
Rx
P4
Tx
P6
Rx
P5
Tx
P3
P2
Rx
Tx
S
ide 2
(End 2)
Side 1
(End 1)
S
ide 2
(End 2)
On EN panels, DKC switches set
the Domain address.
IO Card switches must be set to Off
position, The baud and address
switch settings are now located on DKC
Node 1
Node 3
Node 2
Control panel
Network Card
Address 2
Baud 38.4K
Control panel
Network Card
Address 4
Baud 38.4K
Control panel
Network Card
Address 1
Baud 38.4K
Control panel
IO Card
all switches to
Off position
Network Card
Address 3
Baud 38.4K
Node 4
DKC
Address 1
Baud 19.2K
IO Card
all switches to
Off position
IO Card
all switches to
Off position
DKC
Address 1
Baud 19.2K
DKC
Address 1
Baud 19.2K
IO Card
all switches to
Off position
DKC
Address 1
Baud 19.2K
12 3 456 78
0V -ve +ve 0V I -ve +ve |
P10
Connections for
Network card in
Socket P8 (Card 6)
BACKPLANE
Control Panel
P10
BACKPLANE
Control Panel
Cable screen
Connections for
Network card in
Socket P8 (Card 6)
To Next
panel
or node
From
previous
panel
or node
No
connection
No
connection
12345678
0V -ve +ve 0V I -ve +ve |